hidden

Other application modules

Other application modules is a group holding various application modules.

Micro-ohm

Ground impedance

Step & Touch voltage

Soil resistivity

hidden

Micro-ohm

WARNING
Death or severe injury caused by high voltage possible
Inductive loads may contain a lethal amount of energy if charged with current. The amount of energy depends on the size of the inductive load, the strength of the applied current, and the frequency. To give an example, 350 mJ are assumed as safe according to the safety standard IEC 61010-1. Particularly critical devices are potential transformers or current transformers, but also the inductive part of other test objects can be critical.
  • If you connect loads >0.3 mH to the COMPANO 100 current output I OUT, do not touch the outputs or anything that is connected to them.

  • Make sure that such inductive loads are short-circuited and completely discharged before disconnecting it. In doubt, do not execute resistance tests on inductive loads.

Use the Micro-ohm application module to measure a device under test, for example, a shunt or a closed circuit-breaker, or to verify the integrity of a grounding system by carrying out a ground grid continuity measurement. The ground grid continuity measurement involves measuring the point-to-point resistances within a ground grid. This is to ensure that all parts of the grounding system, e.g. raisers, are properly interconnected with one another. That way, this method detects improper construction work and deterioration.

  1. Use the jog dial wheel to set a current value of your choice at I OUT.

  2. Set the Timeout. 1 second is a good default value to start with.
    To disable the timeout, set it to Off.

  3. Set a proper measurement range depending on the expected result. If in doubt, use the smallest range; the test set will notify you if the measurement range should not be sufficient.

    The 100 mV ranges in QUICK and Micro-ohm are different. The 100 mV range in the Micro-ohm application module uses an additional hardware low-pass filter to suppresses external interferences.
  4. Press the Start/Stop key to start the current output.

  5. It takes a short moment (around 500 ms) for the result to become stable. Then you will get to see the current that COMPANO 100 injected into the device under test, the measured voltage at IN 1, and the resistance value at R.

  6. The measurement stops automatically after the configured Timeout. Press the Start/Stop key to end the measurement manually.

hidden

Ground impedance

A good substation or transmission tower grounding system is crucial to protect people from injury and equipment from damage. International standards such as EN 50522, IEEE Std 80-2013 or IEEE Std 81-2012 give guidelines on how to measure the impedances of such grounding systems.

The Ground impedance application module can test smaller grounding systems with a diameter of up to 30 m/100 ft using an auxiliary current probe. Note: no other grounding system must be nearby.

For grounding systems beyond 30 m/100 ft, which can be found on medium and large distribution substations or transmission substations, preferably use OMICRON’s CPC 100 and CP CU1. With these devices you can use out of service power lines for current injection.

The fall-of-potential method, as it is called in the EN 50522 or IEEE standards, is a good solution for measuring the ground impedance of a substation. The current is fed into a remote ground via a long cable. This remote ground can be any ground from a simple grounding rod to another large grounding system. Usually a grounding rod, referred to as auxiliary current probe, is used.

The distance between this probe and the grounding system under test should be at least five times the diameter of the grounding system. A larger distance will provide more accurate results. In general, the setup must represent worst case conditions that may occur during a single-line fault. This must be clarified for each grounding system individually.

We recommend using an auxiliary current probe as remote ground in 150 m/450 ft distance for grounding systems up to a diameter of 30 m/100 ft.

Then measure the voltages with a second test probe at various distances around the grounding system under test. If possible, choose the measurement points in a 90 º angle (bird’s-eye view) relative to the current path.

We recommend to avoid measuring close to the current path (< 60 º) to reduce the effect of mutual coupling.

The measured data at a large distance away from the grounding grid (typically three times the length of the grounding grid or, for example, 62 % of the injection distance) allow the calculation of the overall ground impedance.


DistanceEN 50522IEEE 81
Auxiliary current probe distance (injection)≥ 4 times the maximum diameter of the grounding system under test but not less than 40 m (130 ft)≥ 5 times the maximum diameter of the grounding system under test
Potential probe distance (measurement) ≥ 2.5 times the diameter of the grounding system in measurement direction but not less than 20 m (65 ft)E.g. 62 % of the distance used for injection

We recommend to measure at different distances. If the distance is high enough, the measurement points should all show similar results. If the points are set too close to the grounding system under test, close to other grounding systems, or over buried pipes, the obtained results are not stable.

Even though this application module is optimized for the fall-of-potential method, it can also be used for the two-point and the three-point method.
 
It is also possible to perform a test using the 62 % rule mentioned in IEEE Std 80-2013 and IEEE Std 81-2012. In this case, perform a single measurement at 62 % (for example, 62 m/200 ft) of the distance of the current probe (for example, 100 m/330 ft) with the current and the potential probe in the same direction.

The example below shows the plot of the resistance in different distances from the grounding grid under test. The ground impedance to distant earth will be about 280 mΩ. By choosing a 90 ° angle for the measurement, there is no risk to get into the influence zone of the auxiliary current probe (marked red below).

hidden

Guided workflow

The ground impedance test incorporates a guided workflow consisting of four steps that can be executed one after another.

It is always possible to return to the menu or to go back to a previous step. For example, it is possible to plot measurements, then go back to the menu and add additional measurements to the previous ones.

Some changes of the settings, such as the output setup, will invalidate results. In such a case, an explicit information dialog is shown.
hidden

Output setup

Use the Output setup feature to find the best output and setting for the measurement. Depending on the impedance of the auxiliary current probe, the best output can be either V OUT or I OUT. If the other output is expected to provide better results, advice is given during the output setup.

WARNING
Death or severe injury caused by high voltage or current possible.
Employ the proper test set.
  • Never use COMPANO 100 to directly inject currents into power cables or overhead lines. If this should become inevitable, use the CPC 100 test set together with CP CU1 and CP GB1.

The auxiliary current probe can carry life-threatening voltages during the test. In case of an error, unexpected high voltages can occur at output I OUT or V OUT at any time. Also the step voltage around the auxiliary current probe can be quite high.
  • Always press the emergency stop button before working with these connectors.

  • Use the provided warning flag*) to mark the auxiliary current probe, or use grounding spikes with safety handle.

  • Mark an area of 5 m/15 ft around the electrode as dangerous zone, and position a guard outside this area to keep people from entering the dangerous zone.

In case of a high-current ground fault within the substation or at the transmission tower during the test, high voltages may occur in any wire connected to the grounding grid or leading away from it.
  • Do not touch the current probe, the potential probe or any wire without insulating gloves.

  • First insert the current probe, then connect it to the provided crocodile clamp. Before removing the current probe, disconnect the crocodile clamp.

 

*) Warning flag for auxiliary current probes provided by OMICRON.

CAUTION
Minor or moderate injury caused by tripping over the measurement cable possible.
  • If the measurement cable crosses obstacles such as roads or walkways, notify approaching persons about the cable to prevent accidents caused by tripping.

Turn the jog dial wheel until the focus is on Output setup. Then press the jog dial wheel once.

The COMPANO 100 test set's V OUT is configured as output by default.

  1. Connect the ground of the grounding system under test to the black socket of V OUT using a measurement cable. Depending of the grounding system, a Kelvin clamp, a Y clamp or Kelvin screws can be the preferred choice.

  2. Depending on the used standard, position the auxiliary current probe at the required distance . If in doubt, choose a 150 m/450 ft distance for grounding systems up to a diameter of 30 m/100 ft.

  3. Connect the auxiliary current probe to the red socket of V OUT using the cable drums and a crocodile clamp.

If at Output setup the power line frequency fNom. is set properly, the suggested frequencies should be 20 Hz above and 20 Hz below the power line frequency. The following steps of the guided workflow consist of two points per measurement with frequency-selective filtering to filter out disturbances of the power line frequency. The result is an interpolation of the two measurement points.

Automated output configuration

For most cases, it is sufficient to use the automated mode.

Press the Start/Stop button for COMPANO 100 to search for the optimum output voltage for the current test setup.

In cases, however, where the ground injection point has a particularly low impedance, it could be that, after the automated setup, the lower part of the display suggests I OUT being the better choice for the output. In such a case, simply rewire from V OUT to I OUT, and repeat the automated setup.

Manual output configuration:

In certain cases, it makes sense to apply a manual output setup configuration. To do so, switch to Manual and set the individual parameters manually. The closer you set the ± delta frequency value towards the nominal frequency fNom., the steeper the used filters operate. Consequently, measurements very close to the nominal frequency have a better noise suppression, but they also need a bit longer. The default with ±20 Hz was primarily chosen for compatibility reasons with CPC 100 and HGT1 measurements.

Other frequency values can make sense when the system frequency differs from the power line frequency, for example, in 16.7 Hz or 25 Hz railway systems. In such cases, reducing the ± delta frequency to a minimum value (> 0 Hz) proves advantageous. It is also possible to set the ± delta frequency to 0 Hz in order to perform a measurement at a single frequency. This can be used if, for example, measurements at 128  Hz are required, which is a common measurement frequency for some grounding testers.

In general, we suggest to increase the magnitude as much as possible, whereat V OUT currents slightly above 200 mA are possible. When you are in manual mode, the lower part of the display shows hints helping you to find the best output configuration.

By pressing the To menu soft key you can return to the guided workflow overview. Nevertheless, the configured settings are remembered for the following steps.

hidden

Reduction factor

Turn the jog dial wheel until the focus is on Reduction factor. Then press the jog dial wheel once.

Reduction factors need to be considered on grounding systems if they are connected to other grounding systems, e.g. via overhead wires on transmission towers or via underground cables.

For typical examples of current reduction → Reduction factor.

The ratio (magnitude and phase angle) between effective local ground current and injected current is called current reduction factor r:

The term "current reduction factor" may be a bit misleading. Please note:

In COMPANO 100, the current reduction factor can be entered manually when it is known , or it can be measured.

Entering the current reduction factor manually:

When you know the current reduction factor, enter its magnitude and phase angle. A current reduction factor of 1 is common, for example, on a transmission tower with no ground wire or with an insulated one. For a current reduction factor of 1, generally 0 ° is set.

Measuring the current reduction factor:

Usually, the current reduction factor is unknown and needs to be measured.

You typically measure current reduction with a Rogowski coil. In many cases, like at a transmission tower, it is not possible to measure all currents in one step, so you have to carry out more than one measurements. These measurements can be performed one after another. COMPANO 100 will then automatically calculate the resulting overall current reduction factor r based on magnitudes and phases of all measurements.

It is highly important to carry out the current reduction factor measurements very thoroughly. Each Rogowski coil has a small arrow imprinted on it. Make sure it points into the right direction. If one single measurement is accidentally done wrong, the result of the entire ground impedance measurement will be wrong.

Some Rogowski coils have integrated power-off functions, which may switch off the measurement after a few minutes. The measurement result will be invalid in this case. Check the user documentation of your sensor on how this function works or how to disable it for the measurement. If in doubt, switch off the sensor and activate it again shortly before a measurement is performed.

It is possible to measure the current "above" or "below" the current injection point.

Performing the measurement:

  1. Configure the measurement range on the Rogowski coil. Use the smallest feasible range to increase measurement accuracy.

  2. Set the IN1 input ratio to the current measurement ratio of the Rogowski coil in the selected range, for example, 100.0 mV/A or 1.0 V/A.

    Tips:

  3. Install the Rogowski coil, for example, on a leg of the transmission tower or around a low voltage cable in a distribution substation, then connect it to the IN1 input. Verify correct polarity.

  4. Press the Start/Stop button of the COMPANO 100 test set to output the test current and to carry out the measurement.

    The measurement will be performed with the configured frequencies, and interpolated to the specified nominal frequency. Additionally, the reduction factor value in the display will be updated.

    • Check the current shown in the display. It should show approximately the same value as the current displayed during the output setup. If it is significantly lower, the cause may be a loose connection at the cables used for current injection.

    • Check the voltage shown in the display. It should exceed 1 mV. If it is significantly lower, the cause may be a loose connection at the cables used to connect the potential probe.

  5. Repeat steps 3 and 4, if needed (for example, on all four legs of a transmission tower or on all cable connections to other grounding systems).

All measurements have a unique ID number. If needed, individual measurements can be deleted. To do so, select the measurements using the jog dial wheel, press the wheel, select the measurement to delete, then press Delete selected.

We recommend to thoroughly document what ID is used for what current path. Add a photograph, if possible, showing the direction arrow of the Rogowski coil. For that reason, the IDs are not changed if a result is deleted later.

The current reduction factor is calculated from the measurements. If it goes beyond 1 or below 0, there is an error in the measurement setup.

Tip: If you doubt that your measurement is correct, you can carry it out with the other current direction, too. If there are major deviations, either an error occurred (for example, wrong direction of the arrow on the Rogowski coil, loose cable contact,...) or the injected current was too small for an accurate measurement result.

By pressing the To menu soft key you can return to the guided workflow overview. Nevertheless, the reduction factor (entered or measured) is remembered for the following steps.

hidden

Measurements

Measurement setup:

Note: The point of current injection, which was defined and configured in the step Output setup, will not be altered in this chapter. It stays where it is throughout the whole procedure.

WARNING
Death or severe injury caused by high voltage or current possible.
In case of a high-current ground fault within the substation or at the transmission tower during the test, high voltages may occur in any wire connected to the grounding grid or leading away from it.
  • Do not touch the current probe, the potential probe or any wire without insulating gloves.

  • First insert the current probe, then connect it to the provided crocodile clamp. Before removing the current probe, disconnect it.

  1. Make sure that the auxiliary current probe connected to V OUT is positioned away from the COMPANO 100 test set at least 5 × the diameter of the grounding system of the transmission tower (or the substation). For that purpose, OMICRON provides 150 m of cable.

  2. Connect the black socket of the measurement input IN 1 to the grounding grid under test, e.g. using the same Kelvin clamp, Y clamp or Kelvin screw as for the current injection (→ Output setup).

  3. Position the potential probe into the soil at the required distance from the grounding system, and connect it with a crocodile clamp and the supplied cable drums to the red socket of the measurement input IN 1. If you apply the fall-of-potential method, we recommend an initial distance of 1 m/3 ft.

  4. Turn the jog dial wheel until the focus is on Measurements. Then press the jog dial wheel once.

  5. Enter the measured distance to the grounding system under test into the software, then press the Start/Stop key.

    Press the Start/Stop key

    After a short time, COMPANO 100 will stop and show a first result.

    Check the current shown in the display. It should show approximately the same value as the current displayed during the output setup. If it is significantly smaller, the cause may be a loose connection at the cables used for current injection.
  6. Now repeat that procedure by positioning the potential probe at several spots with "logarithmically" increasing distances, for example 2 m, 5 m, 10 m, 15 m, 20 m, 30 m, 40 m, 50 m, 70 m, 80 m, 100 m.

The results can be displayed with or without the current Reduction factor taken into account.

You can also switch between Z/Phi and R/X representation of the impedance values.

By pressing the To menu soft key you can return to the guided workflow overview. The results are kept.

hidden

Plot

The plot displays the measured impedances at the various distances and states whether a reduction factor applies.

You can enter an expected maximum current towards earth in case of a fault. The second axis of the graph displays the expected ground potential raise at the various distances.

hidden

Results

The results can be stored on a USB stick.

Excel File Loader

The Ground Impedance EXCEL template, provided with the COMPANO Excel File Loader, can be used to load the measurement, and to generate a report.

hidden

Step and touch voltage

A step and touch voltage test is carried out to determine

The Step and touch voltage application module of COMPANO 100 acts as a source for the HGT1 accessory from OMICRON.

The HGT1 is an FFT voltmeter, primarily designed for professional acoustical test applications. For step and touch voltage and ground impedance measurements, HGT1 is delivered with an OMICRON software that allows measuring the frequency-selective voltage level by using a real-time Zoom FFT. HGT1 works as an add-on device to COMPANO 100, CPC 100 and CP CU1.

For more information about measuring with HGT1Accessory HGT1.

With COMPANO 100, it is possible to measure the step and touch voltages in smaller grounding systems with a diameter of up to 30 m/100 ft.

For grounding systems beyond 30 m/100 ft, which can be found on medium and large distribution substations or transmission substations, preferably use OMICRON’s CPC 100 and CP CU1. With these devices you can use out of service power lines for current injection.

During a step and touch voltage test, the current is fed into a remote ground via a long cable. This remote ground can be any ground from a simple grounding rod to another large grounding system. Usually a grounding rod, referred as auxiliary current probe, is used. The distance between this probe and the grounding system under test should be at least five times the diameter of the grounding system. A larger distance will provide more accurate results. In general, the setup must represent worst case conditions that may occur during a single-line fault. This must be clarified for each grounding system individually.

We recommend using an auxiliary current probe as remote ground in 150 m/450 ft distance for grounding systems up to a diameter of 30 m/100 ft.
hidden

Guided workflow

The step and touch setup incorporates a guided workflow that consists of three steps, which are executed one after another. The third step generates the desired output signal, only. Do the actual measurement with HGT1.

hidden

Output setup

Use the Output setup feature to find the best output and setting for the measurement. Depending on the impedance of the auxiliary current probe, the best output can be either V OUT or I OUT. If the other output is expected to provide better results, advice is given during the output setup.

WARNING
Death or severe injury caused by high voltage or current possible.
Employ the proper test set.
  • Never use COMPANO 100 to directly inject currents into power cables or overhead lines. If this should become inevitable, use the CPC 100 test set together with CP CU1 and CP GB1.

The auxiliary current probe can carry life-threatening voltages during the test. In case of an error, unexpected high voltages can occur at output I OUT or V OUT at any time. Also the step voltage around the auxiliary current probe can be quite high.
  • Always press the emergency stop button before working with these connectors.

  • Use the provided warning flag*) to mark the auxiliary current probe, or use grounding spikes with safety handle.

  • Mark an area of 5 m/15 ft around the electrode as dangerous zone, and position a guard outside this area to keep people from entering the dangerous zone.

In case of a high-current ground fault within the substation or at the transmission tower during the test, high voltages may occur in any wire connected to the grounding grid or leading away from it.
  • Do not touch the current probe, the potential probe or any wire without insulating gloves.

  • First insert the current probe, then connect it to the provided crocodile clamp. Before removing the current probe, disconnect the crocodile clamp.

 

*) Warning flag for auxiliary current probes provided by OMICRON.

CAUTION
Minor or moderate injury caused by tripping over the measurement cable possible.
  • If the measurement cable crosses obstacles such as roads or walkways, notify approaching persons about the cable to prevent accidents caused by tripping.

Turn the jog dial wheel until the focus is on Output setup. Then press the jog dial wheel once.

The COMPANO 100 test set's V OUT is configured as output by default.

  1. Connect the ground of the grounding system under test to the black socket of V OUT using a measurement cable. Depending of the grounding system, a Kelvin clamp, a Y clamp or Kelvin screws can be the preferred choice.

  2. Depending on the used standard, position the auxiliary current probe at the required distance . If in doubt, choose a 150 m/450 ft distance for grounding systems up to a diameter of 30 m/100 ft.

  3. Connect the auxiliary current probe to the red socket of V OUT using the cable drums and a crocodile clamp.

If at Output setup the power line frequency fNom. is set properly, the suggested frequencies should be 20 Hz above and 20 Hz below the power line frequency. The following steps of the guided workflow consist of two points per measurement with frequency-selective filtering to filter out disturbances of the power line frequency. The result is an interpolation of the two measurement points.

Automated output configuration

For most cases, it is sufficient to use the automated mode.

Press the Start/Stop button for COMPANO 100 to search for the optimum output voltage for the current test setup.

In cases, however, where the ground injection point has a particularly low impedance, it could be that, after the automated setup, the lower part of the display suggests I OUT being the better choice for the output. In such a case, simply rewire from V OUT to I OUT, and repeat the automated setup.

Manual output configuration:

In certain cases, it makes sense to apply a manual output setup configuration. To do so, switch to Manual and set the individual parameters manually. The closer you set the ± delta frequency value towards the nominal frequency fNom., the steeper the used filters operate. Consequently, measurements very close to the nominal frequency have a better noise suppression, but they also need a bit longer. The default with ±20 Hz was primarily chosen for compatibility reasons with CPC 100 and HGT1 measurements.

Other frequency values can make sense when the system frequency differs from the power line frequency, for example, in 16.7 Hz or 25 Hz railway systems. In such cases, reducing the ± delta frequency to a minimum value (> 0 Hz) proves advantageous. It is also possible to set the ± delta frequency to 0 Hz in order to perform a measurement at a single frequency. This can be used if, for example, measurements at 128  Hz are required, which is a common measurement frequency for some grounding testers.

In general, we suggest to increase the magnitude as much as possible, whereat V OUT currents slightly above 200 mA are possible. When you are in manual mode, the lower part of the display shows hints helping you to find the best output configuration.

By pressing the To menu soft key you can return to the guided workflow overview. Nevertheless, the configured settings are remembered for the following steps.

hidden

Reduction factor

Turn the jog dial wheel until the focus is on Reduction factor. Then press the jog dial wheel once.

Reduction factors need to be considered on grounding systems if they are connected to other grounding systems, e.g. via overhead wires on transmission towers or via underground cables.

For typical examples of current reduction → Reduction factor.

The ratio (magnitude and phase angle) between effective local ground current and injected current is called current reduction factor r:

The term "current reduction factor" may be a bit misleading. Please note:

In COMPANO 100, the current reduction factor can be entered manually when it is known , or it can be measured.

Entering the current reduction factor manually:

When you know the current reduction factor, enter its magnitude and phase angle. A current reduction factor of 1 is common, for example, on a transmission tower with no ground wire or with an insulated one. For a current reduction factor of 1, generally 0 ° is set.

Measuring the current reduction factor:

Usually, the current reduction factor is unknown and needs to be measured.

You typically measure current reduction with a Rogowski coil. In many cases, like at a transmission tower, it is not possible to measure all currents in one step, so you have to carry out more than one measurements. These measurements can be performed one after another. COMPANO 100 will then automatically calculate the resulting overall current reduction factor r based on magnitudes and phases of all measurements.

It is highly important to carry out the current reduction factor measurements very thoroughly. Each Rogowski coil has a small arrow imprinted on it. Make sure it points into the right direction. If one single measurement is accidentally done wrong, the result of the entire ground impedance measurement will be wrong.

Some Rogowski coils have integrated power-off functions, which may switch off the measurement after a few minutes. The measurement result will be invalid in this case. Check the user documentation of your sensor on how this function works or how to disable it for the measurement. If in doubt, switch off the sensor and activate it again shortly before a measurement is performed.

It is possible to measure the current "above" or "below" the current injection point.

Performing the measurement:

  1. Configure the measurement range on the Rogowski coil. Use the smallest feasible range to increase measurement accuracy.

  2. Set the IN1 input ratio to the current measurement ratio of the Rogowski coil in the selected range, for example, 100.0 mV/A or 1.0 V/A.

    Tips:

  3. Install the Rogowski coil, for example, on a leg of the transmission tower or around a low voltage cable in a distribution substation, then connect it to the IN1 input. Verify correct polarity.

  4. Press the Start/Stop button of the COMPANO 100 test set to output the test current and to carry out the measurement.

    The measurement will be performed with the configured frequencies, and interpolated to the specified nominal frequency. Additionally, the reduction factor value in the display will be updated.

    Check the current shown in the display. It should show approximately the same value as the current displayed during the output setup. If it is significantly smaller, the cause may be a loose connection at the cables used for current injection.
  5. Repeat steps 3 and 4, if needed (for example, on all four legs of a transmission tower or on all cable connections to other grounding systems).

All measurements have a unique ID number. If needed, individual measurements can be deleted. To do so, select the measurements using the jog dial wheel, press the wheel, select the measurement to delete, then press Delete selected.

We recommend to thoroughly document what ID is used for what current path. Add a photograph, if possible, showing the direction arrow of the Rogowski coil. For that reason, the IDs are not changed if a result is deleted later.

The current reduction factor is calculated from the measurements. If it goes beyond 1 or below 0, there is an error in the measurement setup.

Tip: If you doubt that your measurement is correct, you can carry it out with the other current direction, too. If there are major deviations, either an error occurred (for example, wrong direction of the arrow on the Rogowski coil, loose cable contact,...) or the injected current was too small for an accurate measurement result.

By pressing the To menu soft key you can return to the guided workflow overview. Nevertheless, the reduction factor (entered or measured) is remembered for the following steps.

hidden

Output

Turn the jog dial wheel until the focus is on Output. Then press the jog dial wheel once.

You can vary the on, off and pause time to meet your needs. Press the Start/Stop key to start the output sequence. That sequence is repeated until manually stopped.

The pause time is meant to save battery power on long testing days.

We recommend synchronizing the start of the measurement with the beginning of a new minute. That way you can expect a new measurement of the HGT1 at every full and half minute if, for example, a total time of 30 seconds is used. This is useful if measurement points are far away, and you are not sure whether or not you can still measure a signal.

For more information about measuring with HGT1Accessory HGT1.

hidden

Results

The results can be stored on a USB stick. They contain the used frequencies, the output current, and the reduction factor.

The Step and Touch Voltage EXCEL template, provided with the COMPANO Excel File Loader, can be used to load the data from both the COMPANO 100 test set and the HGT1, and to generate a report.

For more information about the Excel File LoaderExcel File Loader.

For more information about recording and saving step and touch voltage measurements with HGT1, please refer to the HGT1 User Manual.

hidden

Soil resistivity

A soil resistivity test is performed prior to the construction of a grounding system in order to know about the resistivity of the soil in different layers. Its measurement results can be furthermore used in conjunction with grounding grid calculation and simulation software such as CDEGS.

The measurement delivers specific soil resistivity values for different distances between the used current and potential probes that allow drawing conclusions about the layers in the ground in larger depths.

The soil resistivity application module allows performing this test and directly evaluating the results using either the Wenner or Schlumberger method. For example, the Wenner method is shown below

The soil resistivity application module incorporates a guided workflow that consists of two steps, which can be executed one after another.

hidden

Output setup

WARNING
Death or severe injury caused by high voltage or current possible.
In the unlikely event of an internal error of the COMPANO 100 test set, higher voltages than expected could occur at output V OUT.
  • Always press the emergency stop button before working with these connectors.

  • Mark an area of 5 m/15 ft around the electrode as dangerous zone, and position a guard outside this area to keep people from entering the dangerous zone.

The Output setup is configured to use V OUT with 40 V in the soil resistivity application module. Since for most cases, there is no need to change this configuration, you may skip this step and progress directly to the measurement step.

However, if there are exceptional circumstances, such as a very conductive soil, reduce the voltage as the resulting current might be too high for the voltage output. In such a case, the COMPANO 100 test set would switch off with an error message. If this happens, reduce the voltage, and try again.

If the voltage needs to be adjusted, turn the jog dial wheel until the focus is on Output setup. Then press the jog dial wheel once.

A delta frequency value of ±20 Hz from the power line frequency is generally a good choice. If needed, the value can be changed, though. It is also possible to set it to 0 Hz in order to perform a measurement at a single frequency. This can be used, if you, for example, require measurements at 128 Hz, which is a common measurement frequency for some grounding testers.

You can test the output configuration by pressing the Start/Stop key.

By pressing the To menu soft key you can return to the guided workflow overview. Nevertheless, the configured settings are remembered for the following step.

hidden

Measurements

The soil resistivity measurement screen displays the wiring setup.

COMPANO 100 supports three different methods for soil resistivity measurements.

WARNING
Death or severe injury caused by high voltage or current possible.
In the unlikely event of an internal error of the COMPANO 100 test set, higher voltages than expected could occur at output V OUT.
  • Always press the emergency stop button before working with these connectors.

  • Mark an area of 5 m/15 ft around the electrode as dangerous zone, and position a guard outside this area to keep people from entering the dangerous zone.

Performing the measurement:

  1. Select the measurement method of your choice.

    The different methods (Wenner/Schlumberger) cannot be mixed.

  2. Place the grounding probes as shown on the display.

  3. Connect the probes to the V OUT output and the IN 1 input of the COMPANO 100 test set. To do so, use the provided measurement cables and crocodile clamps.

  4. Enter the distances to the table of the Soil resistivity screen.

  5. Press the Start/Stop key on the COMPANO 100 test set to output the test current and to carry out the measurement. The measurement will be performed with the configured frequencies, and interpolated to the specified nominal frequency.

  6. Repeat steps 3 to 5 for all measurement distances.

After the measurement, the result will be shown with a unique ID in the results list. To delete individual or all results, select the list with the jog dial wheel.

The result is shown as specific soil resistivity ρ in Ωm. Alternatively, you can also display them as raw impedance value |Z| in Ω. The raw values |Z| can be used to calculate the soil resistivity manually. This is useful if other methods are used, such as the Pole-Dipole or the Dipole-Dipole method.

Typical resistivity of common soil types:

Soil typeSoil resistivity
Moor, marsh, very moist soil1 ... 50 Ωm
Loess, clay20 ... 100 Ωm
Humus, acre10 ... 200 Ωm
Sandy clay50 ... 500 Ωm
Stony, grassy soil100 ... 300 Ωm
Glass sand200 ... 3000 Ωm
Rock300 ... 5000 Ωm
Granite, freestone1500 ... 10000 Ωm

Soil resistivity is a major factor for the corrosiveness of soil:

Corrosiveness of soilSoil resistivity
Severe< 10 Ωm
Corrosive10 ... 50 Ωm
Moderately corrosive50 ... 100 Ωm
Slightly corrosive100 ... 500 Ωm

hidden

Results

The results can be stored on a USB stick.

The COMPANO Excel File Loader can be used to load the data from the COMPANO 100 test set. Afterwards, the data can be copied, for example, into a grounding system calculation software.

For more information about the Excel File LoaderExcel File Loader.