hidden

FLEX

Use FLEX to define and output a sequence of steps. Such a sequence step can be a signal state (a constant current or voltage output, for example), a ramp, or a pulse ramp. Each sequence step has a trailing transition that you can parameterize.

Contrary to QUICK, in FLEX you define the output parameters prior to the output generation. While the outputs are active, you cannot change the parameters anymore.

Entering parameters:

  1. Turn the jog dial wheel until the focus is on the field of your choice.
  2. Press the jog dial wheel, then turn it again to set a value. Alternatively, rather than turning the wheel, press a soft key of your choice to apply its value to the input field. By turning the jog dial wheel again, you can change that value.
  3. Press the jog dial wheel again to acknowledge your set value, then navigate to the next field.

Example: You have set an I OUT of 9.5 A for sequence step 1. If you now define a timeout of 1 s (60 cycles) for that sequence step, you have defined a start value for your test of 9.5 A at I OUT that after 1 s progresses to the sequence step transition, and from there to sequence step 2.

Sequence step transition

The transition from one sequence step to another can be:

Note: The open/close detection as described in chapter QUICK (see QUICK ► note reg. the open/close detection function) is disabled in the FLEX application module for full dynamic response to sudden load changes, for example, when electro-mechanical relays pick up.
hidden

Sequence step transition "step"

"Step" is a non-configurable transition at the end of a sequence step. Nothing happens in this transition; the sequence step n progresses immediately to the next sequence step n+1.

With such step transitions in between the individual steps you can define a sequence whose steps are either triggered by events such as overloads or binary triggers, or by timeouts.

The overload indicator is delayed by 200 ms in either direction, coming and going. This is necessary to suppress short spikes of the detection, on one hand, and, on the other hand, to reliably evaluate that the overload has finally cleared instead of just disappearing temporarily like, for example, during zero crossing. This means, if you do a time measurement using "Overload" triggers, add to or deduct from the result 200 ms, accordingly.
hidden

Sequence step transition "ramp"

The transition from sequence step n to the next sequence step n+1 is a ramped signal.

hidden

Sequence step transition "pulse ramp"

The transition from sequence step n to the next sequence step n+1 is a pulse-ramped signal.

Tips & Tricks

In general, a pulse ramp would be defined as shown in the left part of the picture below.

Testing, for example, the high setting of an instantaneous trip could take very long that way. There is a quicker way to do this:

  1. Define a state with the pre-fault value and with a timeout as long as needed.

  2. Define a second state with the start value of the pulse ramp (red arrow) and with a timeout of 1 ms, only. This will not considerably affect the first pulse, but it will define the start point.

  3. Then define the pulse ramp with the same reset value like the one that you have set for the pre-fault state.

  4. Setting a reset value other than zero (for example, the nominal value) can be advantageous. In many cases the relay needs that, and COMPANO 100 can output a better signal quality if there is no complete interruption.

hidden

Sequence step transition "smooth ramp"

The transition from sequence step n to the next sequence step n+1 is a continuous smooth ramp.

The smooth ramp changes the output value frequently. In the default setting, the timer resets each time when the output changes. This means that, by default, it shows no meaningful value if smooth ramps are used. If you would like to use the timer to measure a trip time of a dI/dt or df/ft relay, instead of output change, reconfigure the timer to start at the state transition from the previous state to the current state.

Tips & Tricks

Usually, smooth ramps are used to test protection functions like df/dt or dI/dt. When the configured slew rate is exceeded, the relay must trip within a certain time.

Step 1Step 2Step 3

For example, 50 HzFor example, 0.9 Hz/sFor example, 1.1 Hz/s

 

Example of how this could be tested:

  1. Define a state with the pre-fault value and with a timeout as long as needed.

  2. Define a smooth ramp with a slew rate slightly below the one to test (for example, 0.9 Hz/s if the relay is configured to trip above 1.0 Hz/s).

  3. Define a smooth ramp with a slew rate slightly above the one to test (for example, 1.1 Hz/s).

  4. Configure the timer to start at the state transition to state 3, and to stop on output halt.

Press the Start/Stop key to execute the sequence.