hidden

QUICK

Check out the COMPANO 100 QUICK video on the OMICRON Video Channel (visit https://www.omicronenergy.com/COMPANO100-Quick).

Use QUICK to directly set the test set’s current output magnitude as well as the frequency of I OUT.

1)In this example, the IN 1 input is configured to be a voltage input. It could as well be a current input, a wet binary input or dry binary input. To change that configuration, press then IN 1 key.
2)Calculated measurement is configured to calculate a power (P) from, for example, current output I OUT and measured voltage at IN 1.
3)You can set a timeout between 1 ms (0.06 cycles at 60 Hz) up to 1 day. While the outputs are active, the timeout counts down. When it reaches zero, the outputs are turned off.

Entering parameters in QUICK:

  1. Turn the jog dial wheel until the focus is on the field of your choice.
  2. Press the jog dial wheel, then turn it again to set a value. Alternatively, rather than turning the wheel, press a soft key of your choice to apply its value to the input field. By turning the jog dial wheel again, you can change that value.
  3. Press the jog dial wheel again to acknowledge your set value and to leave the edit mode. Then navigate to the next field.

To output the set magnitudes at the outputs, and to start the measurements, press the Start/Stop key.

Alternatively, you can activate the test set first, and then set the output values of your choice.

Note: by selecting/clearing the I OUT field, the displayed value toggles between the value of your choice (blue background) and the measured value (white background).

WARNING
Since it is possible to adjust values in real-time by turning the jog dial wheel, death or severe injury can occur if the appropriate safety instructions are not observed.
  • Avoid touching the jog dial wheel by mistake with your body or loose clothing.
  • Make sure that no one stands close to the cable ends at the device under test and/or is able to accidentally touch them while the outputs are on.

Recording results

While the outputs are active, press the Keep result soft key. All values present at the moment of pressing the key are now recorded to an extra tab. You can press Keep result repeatedly; every use of this function will create a new tab. The tabs are numbered consecutively.

One additional tab is created automatically with all present values of the moment you either press the Start/Stop key to turn off the outputs, the timeout feature turns off the outputs, or the trigger to switch off (overload/binary trigger) occurs.

When the measurement is completed, the QUICK tab will be hidden; you will only see the result tabs.

Press the Save soft key to save the results to a USB stick (see Save).

hidden
Note: The QUICK application module supports a special open/close detection function. Very fast changes of the output load are detected as open/close transition, temporarily limiting the output driving voltage and control parameters for about 100 ms to optimize the output behavior for sudden changes between the three states: open circuit, normal load, and short circuit.