hidden

Hardware Configuration

Check out the COMPANO 100 Hardware Configuration video on the OMICRON Video Channel (visit https://www.omicronenergy.com/COMPANO100-Hardware).

Access all individual hardware configurations from the Home screen by selecting the HW Config icon.

Alternatively, just press the respective key below each input/output.

hidden

Configuring I OUT

Press the I OUT key.

Whenever you have made a selection, you are automatically forwarded to the next tab presenting you a new selection to pick from. After the last choice, press the respective application module key to continue measuring.


You have the choice between a 110 A and a 20 A output mode.

Note that the 20 A output limitation provides a slightly more accurate output for small signals than the full-range mode and has a slightly lower compliance voltage. Additionally, the granularity is higher in small current values. In general, in the 20 A mode, currents can be output for a longer period of time. For normal everyday testing, however, this minor accuracy advantage has no big significance.

For measurement purposes, for example, it makes sense to disable both outputs, current and voltage. In such a case the amplifier module is powered down to save battery power.

Note that some application modules overrule the settings of the respective input or output. For example, I OUT is always configured to be a 100 A DC output in Micro-ohm, or always AC in Polarity Check.

hidden

Configuring V OUT (voltage output)

The voltage output V OUT is optional. Please order separately (→ Support).

Press the V OUT key.

You have the choice between output modes AC, DC, and AUX DC.

Whenever you have made a selection, you are automatically forwarded to the next tab presenting you a new selection to pick from. After the last choice, press the respective application module key to continue measuring.


hidden

AUX DC

In the AUX DC mode, the COMPANO 100 can output a higher current and more power – if required even while no test is running.

In the AUX DC view you can set the output voltage, and start and stop the AUX DC voltage output.

The measured current and apparent power are displayed on the right side.

As long as the AUX DC mode is active, the corresponding icon  is displayed in the top right corner of every view:

DANGER
Death or severe injury caused by high voltage
When the warning symbol on the COMPANO 100 front panel is lit and/or the AUX DC icon  is displayed, V OUT carries potentially life-hazardous voltage.
  • Do not leave COMPANO 100 unattended while outputs are active.

  • Stop the AUX DC mode if you are not actively using COMPANO 100.

When you press the emergency stop button, the AUX DC mode is automatically stopped and is not automatically restarted when the emergency stop button is released.
hidden

Configuring IN 1/IN 2 (binary or analog inputs)

Press the IN 1 or IN 2 key.

Whenever you have made a selection, you are automatically forwarded to the next tab presenting you a new selection to pick from. After the last choice, press the respective application module key to continue measuring.


IN 1 and IN 2 can be configured to be either:

By means of a current clamp or a shunt, you can use IN 1 and IN 2 to measure current.

If you do not need these inputs, set them to Off. This keeps the user interface clear because functions set to Off are hidden in, for example, QUICK and FLEX.

IN 1/IN 2 binary

SymbolDryWet

Connected contact openInput voltage below configured threshold or connected contact open.

Connected contact closedInput voltage above configured threshold. Internally uses a voltage hysteresis to suppress interferences.

 

Deglitching input signals:

In order to suppress short spurious pulses, you can configure a deglitching algorithm. The deglitch process results in an additional dead time and introduces a signal delay. In order to be detected as a valid signal level, the level of an input signal must have a constant value at least for the deglitch time.

Input signal

Input signal deglitched
 

 TdeglitchTdeglitch

Debouncing input signals:

For input signals with a bouncing characteristic, you can configure a debounce function. That means, the first bounce of the input signal causes the debounced signal to be changed, too, and then kept on this value for the duration of the debounce time.

The figure below illustrates the debounce function. At the right-hand side of the figure, the debounce time is set too short. As a result, the debounced signal changes to “high” once again, even while the input signal is still bouncing, and does not drop to low level until the expiry of another Tdebounce period.

Input signal

Input signal debounced
 

 TdebounceTdebounceTdebounce

hiddenIN 1/IN 2 analog

Being an analog input, IN 1/IN 2 measures voltage signals up to 300 V AC or DC. By means of a current clamp or a shunt, you can use IN 1/IN 2 to measure current.

COMPANO 100 only measures voltages on IN 1/IN 2 after you have activated the test set by pressing the Start key. Else no measuring takes place. In case you wish to only measure voltage, disable all outputs. Then activate the test set by pressing the Start key.

Note that some application modules overrule the settings of the respective input or output. For example, I OUT is always configured to be a 100 A DC output in Micro-ohm, or always AC in Polarity Check.
hidden

Configuring the timer

The timer can be started and stopped by events you choose. By default, the timer is on.

Examples of timer start/stop events:

Note: In principle, you can define all kinds of triggers you want, regardless whether or not they are feasible. You can, for example, set a transition from sequence step 5 to sequence step 6 in FLEX as trigger having defined three sequence steps, only. In such a case, the trigger condition is never met.

COMPANO 100 only measures timer start/stop events after you have activated the test set by pressing the Start key. Else no measuring takes place. In case you wish to only measure and test timer start/stop events, disable all outputs. Then activate the test set by pressing the Start key.

When the timer stops, the respective screen shows the result. The timer does not restart in such a case; you need to clear the results beforehand. This is why it makes sense, in particular in FLEX applications, not to define an end condition. The timer does not stop, however, with the sequence changes, intermediate results are recorded anyway.

The overload indicator is delayed by 200 ms in either direction, coming and going. This is necessary to suppress short spikes of the detection, on one hand, and, on the other hand, to reliably evaluate that the overload has finally cleared instead of just disappearing temporarily like, for example, during zero crossing. This means, if you do a time measurement using "Overload" triggers, add to or deduct from the result 200 ms, accordingly.
hidden

Reference signals

For phase calculations and certain features, such as the frequency selective measurement (fsel), COMPANO 100 uses an AC reference signal.

This selected reference signal directly affects the measurements done by COMPANO 100 by means of the input signals at IN 1 and IN 2. Should the reference signal be implausible or invalid, all quantities calculated from the reference signal will be wrong. This can happen when, for example, there is nothing connected to the I OUT output or the IN 1/IN 2 inputs but they are set to be a reference signal.

The search for reference signals is done in the below listed order from 1 ... 4. If one of them succeeds to become a reference signal, the rest is ignored.

  1. If I OUT is configured to be an AC output, I OUT is used as reference signal.

  2. Else, if V OUT is configured to be an AC output, V OUT is used as reference signal.

  3. Else, if IN 1 is configured to be an AC input, IN 1 is used as reference signal.

  4. Else, if IN 2 is configured to be an AC input, IN 2 is used as reference signal.

hidden

Configuring calculated measurements

Define a calculated measurement from a combination of two source quantities, such as output current and an input voltage. Depending on the source 1/source 2 combination, different measurements are possible. For example: from an AC voltage and an AC current you can calculate quantities like Z, P or even Rs and Ls. Other combinations, however, such as a binary input and an DC current, do not allow calculated measurements.

COMPANO 100 only carries out a calculated measurement after you have activated the test set by pressing the Start key. Else no measuring takes place. In case you wish to only measure, disable all outputs. Then activate the test set by pressing the Start key.